The low voltage cable with both shielding and armoring not only has excellent anti-electromagnetic interference capability, but can also effectively prevent mechanical damage. It is suitable for places with relatively complex and harsh environments, such as factory workshops, mines, outdoor construction sites and other places. In these places, there may be many sources of electromagnetic interference, and at the same time, the cables are also prone to mechanical damage from external force. The armoring layer can protect the cables from physical damage, while the shielding layer can resist electromagnetic interference and ensure the normal transmission of electricity or signals.
| Nominal cross section (mm2) |
Nom. insulation thick. (mm) |
Nom. sheath thick. (mm) |
Approx. overall diam. (mm) |
Conductor max. DC resistance at 20°C (Ω/km) |
Conductor short-circuit current (kA/1s) |
||
| Copper | Aluminum | Copper | Aluminum | ||||
| 1.5 | 0.7 | 1.4 | 5.6 | 12.1 | – | 0.21 | – |
| 2.5 | 0.7 | 1.4 | 6 | 7.41 | – | 0.36 | – |
| 4 | 0.7 | 1.4 | 6.5 | 4.61 | – | 0.57 | – |
| 6 | 0.7 | 1.4 | 7 | 3.08 | – | 0.86 | – |
| 10 | 0.7 | 1.4 | 8 | 1.83 | 3.08 | 1.43 | 0.95 |
| 16 | 0.7 | 1.4 | 9 | 1.15 | 1.91 | 2.29 | 1.51 |
| 25 | 0.9 | 1.4 | 10.6 | 0.727 | 1.2 | 3.58 | 2.36 |
| 35 | 0.9 | 1.4 | 11.6 | 0.524 | 0.868 | 5.01 | 3.31 |
| 50 | 1 | 1.4 | 13 | 0.387 | 0.641 | 7.15 | 4.73 |
| 70 | 1.1 | 1.4 | 15 | 0.268 | 0.443 | 10.02 | 6.62 |
| 95 | 1.1 | 1.5 | 16.7 | 0.193 | 0.32 | 13.59 | 8.98 |
| 120 | 1.2 | 1.5 | 18.4 | 0.153 | 0.253 | 17.17 | 11.35 |
| 150 | 1.4 | 1.6 | 20.5 | 0.124 | 0.206 | 21.46 | 14.18 |
| 185 | 1.6 | 1.6 | 22.7 | 0.0991 | 0.164 | 26.47 | 17.49 |
| 240 | 1.7 | 1.7 | 25.4 | 0.0754 | 0.125 | 34.34 | 22.69 |
| 300 | 1.8 | 1.8 | 27.8 | 0.0601 | 0.1 | 42.93 | 28.36 |
| 400 | 2 | 1.9 | 31.5 | 0.047 | 0.0778 | 57.23 | 37.82 |
| 500 | 2.2 | 2 | 35.1 | 0.0366 | 0.0605 | 71.54 | 47.27 |
| 630 | 2.4 | 2.2 | 39.3 | 0.0283 | 0.0469 | 90.14 | 59.56 |
| 800 | 2.6 | 2.3 | 44.3 | 0.0221 | 0.0367 | 114.47 | 75.64 |
Note: The above is only part of the product specifications and technical parameters, if you need detailed parameters, please contact our sales manager.
IPCI in Kazakhstan (End Client: CNCEC, Kazakhstan)

Karot Hydropower Station Project in Pakistan (End Client: KAROT POWER COMPANY(PVT) LIMITED, Pakistan)

Please provide the following details to help our sales representatives better understand your needs and get In touch with you as soon as possible.
Connecting Wonderful Life With Optic-Electric Network
Products
Quick Link