245kV GIS/Transformer Termination

It’s applicable to connect extruding HV cables to GIS equipment and transformer,it is suitable for  XLPE or EPR insulated cables with copper, aluminum or aluminum alloy conductors.

Voltage (kV) 245
Insulation Diameter(mm) Φ80.6~Φ125.6
Cross section Area of cable conductor(mm2) 400-3500mm²
The conductor connection method Crimping Bolt shear
 
Testing items Testing contents value
AC withstand Test Dry AC withstand test 254kV 15min
Impulse test Lightning impulse 1050kV, ±10 times
Current carrying capacity Rate current
Short-circuit current
By cable spec
Stress cone electrical
performance
AC withstand test
Partial discharge test
318kV 30min
As 190kV,≤5pC

The information of dimension and weight

Products Type The height (mm) The weight (kG)
Short Type 1350 155
Long Type 1700 165