It is applicable to connect the extruding HV cables each other, suitable for XLPE or EPR insulated cables with copper, aluminum or aluminum alloy conductors.
| Voltage (kV) | 123 |
| Insulation Diameter(mm) | Φ54~Φ91.6 |
| Cross section Area of cable conductor(mm2) | 240-2000mm² |
| The conductor connection method | Crimping Bolt shear |
| Testing items | Testing contents | value |
| AC withstand Test | Dry AC withstand test | 160kV 15min |
| Impulse test | Lightning impulse | 550kV, ±10 times |
| Current carrying capacity | Rate current Short-circuit current |
By cable spec |
| Stress cone electrical performance |
AC withstand test Partial discharge test |
160kV 30min As 96kV,≤5pC |
| Shield interruption test | Lightning Impulse test DC withstand test |
37.5kV,±10 times 25kV 1min |
The information of dimension and weight
The length with copper housing:1500mm,the weight with copper housing:70kg;
The length with copper housing/coffin box:2200mm,
the weight with copper housing/coffin box:150kg
It is applicable to connect the extruding HV cables each other, suitable for XLPE or EPR insulated cables with copper, aluminum or aluminum alloy conductors.