HTLS Invar Conductor(STACIR/AS, ZTACIR/AS)

Super Thermal-resistant Aluminum-alloy Conductor Aluminum-clad Invar Reinforced

  • Super thermal resistant aluminum alloy, double current-carrying capacity at continuous working temperature 210℃.
  • Aluminium-clad invar steel core, with very low thermal expansion coefficient.
  • High temperature low sag performance, upgrading the line capacity without replacing tower, saving space and land resources.
  • Convenient installation, installation method is same as ACSR conductor.

ZTT® ET EXPRESSWAY ESSENCETM ZTACIR/AS350/45

 

Conductor Technical Structure

Parameter Unit Value
Structure Center: Aluminum clad Invar wire Nos./mm 1/2.88
Layer 1: Aluminum clad Invar wire 6/2.88
Layer 2: ZTAL wire* 9/4.32
Layer 3: ZTAL wire 15/4.32
Standard / IEC 61089/ 62641/ 63248
Stranding direction of outer layer Direction Right-hand
Conductor diameter mm 25.92
Cross section ZTAL wire mm2 351.78
Aluminum-clad Invar wire 45.6
Total 397.38
Conductor weight kg/km 1309
Rated tensile strength kN 103.1
Modulus of Elasticity (E-Modulus) kN/mm2 67.05 /160 (Above Knee Point)
Linear expansion coefficient 10-6/℃ 17.52 / 3.0 (Above Knee Point)
DC Resistance at 20℃ Ω/km 0.0816
Max. Working temperature Continuous 210 (40 years)
Short term 240 (400 hours)
Lay ratio ZTAL layer times 15-wire layer 10-14
9-wire layer 10-16
Aluminum clad invar layer 6-wire layer 16-26

*ZTAL wire: Super thermal resistant aluminum alloy wire AT3

Transmission of high current carrying capacity, suitable for line upgrading without replacing tower. High temperature low sag performance, increase current capacity by 100%, yet no need to replace tower.

Let’s Build The Future with Innovation

Please provide the following details to help our sales representatives better understand your needs and get In touch with you as soon as possible.