ZTT® ET EXPRESSWAYTM TACSR–400/35

Conductor Technical Structure
| Parameter | Unit | Value | |
| Structure | Center: Steel wire | Nos./mm | 1/2.50 |
| Layer 1: Steel wire | 6/2.50 | ||
| Layer 2: TAL* wire | 10/3.22 | ||
| Layer 3: TAL wire | 16/3.22 | ||
| Layer 4: TAL wire | 22/3.22 | ||
| Standard | / | IEC 61089/ 62641/ 63248 | |
| Stranding direction of outer layer | Direction | Right-hand | |
| Conductor diameter | mm | 26.82 | |
| Cross section | Steel wire | mm2 | 34.4 |
| TAL* wire | 390.9 | ||
| Total | 425.3 | ||
| Conductor weight | kg/km | 1348.7 | |
| Rated tensile strength | kN | 102.5 | |
| Modulus of Elasticity | GPa | 66.3 | |
| Coefficient of linear expansion | 10-6/℃ | 20.3 | |
| Continuous operation temperature | ℃ | 150 | |
| Max. DC Resistance at 20℃ | Ω/km | 0.07516 | |
| Lay ratio | TAL wire layer | times | 22 wires layer: 10-14 |
| 16 wires layer: 10-16 | |||
| 10 wires layer: 10-16 | |||
| Steel wire layer | 6-wire layer: 16-26 | ||
Medium distance overhead line, suitable for transmission of high current carrying capacity and upgrading of transmission line.
Please provide the following details to help our sales representatives better understand your needs and get In touch with you as soon as possible.
Connecting Wonderful Life With Optic-Electric Network
Products
Quick Link