Technical Specifications of 280Ah Outdoor Liquid Cooling Battery Cabinet
344KWh 1500V Outdoor Liquid Cooling Battery Cabinet
Product Features
Technical Indicators
| 215KWh liquid cooling energy storage cabinet | ||
| AC side parameters | Rated AC power | 105kVA |
| Wiring method | Three-phase four-wire | |
| AC overload capability | 116kVA | |
| Allowable grid voltage | 380/400 (-15%~15%)Vac | |
| Permitted grid frequency | 50/60 (-2.5~2.5) Hz | |
| Total current harmonic distortion | ≤3% | |
| Power Factor | 0.99/-1~1 | |
| DC side parameters | Battery Type | Lithium iron phosphate battery |
| Combination | 48S1P *5 | |
| Nominal voltage | 768 V | |
| Voltage range | 624 ~ 864 V | |
| Nominal power | 215 kWh | |
| Nominal capacity | 280Ah | |
| System efficiency | ≥93 % | |
| Other parameters | Operating temperature range | -20-55℃(Decrease power when it is above 45℃) |
| Operating humidity | 5%~95% (No condensation) | |
| Operating altitude | 3000m ( Decrease power when it is over 3000m) | |
| Temperature control solution | Liquid cooling | |
| Fire protection plan | PERFLUORO and water spray | |
| Protection level | IP54 | |
| Corrosion resistance grade | C3 | |
| Noise | ≤ 75 db | |
| Wire Inlet and outlet | Wire in and out from underneath | |
| Dimension (length * depth *height ) | 1404*1360*2000 mm | |
| Communication protocol | Modbus-RTU , Modbus-TCP , IEC104 , IEC61850 , CAN2.0 , etc. | |
| Communication mode | RS 485 , Ethernet , CAN , dry contact, etc. | |