245 kV Composite/ Porcelain Outdoor Termination

It is applicable to connect extruding HV cables to outdoor electrical equipment and overhead lines,it is suitable for XLPE or EPR insulated cables with copper, aluminum or aluminum alloy conductors.

Voltage (kV) 245
Insulation Diameter(mm) Φ80.6~Φ125.6
Cross section Area of cable conductor(mm2) 400-3500mm²
The conductor connection method Crimping Bolt shear
 
Testing items Testing contents value
AC withstand Test Dry AC withstand test 254kV 15min
Impulse test Lightning impulse 1050kV, ±10 times
Current carrying capacity Rate current
Short-circuit current
By cable spec
Stress cone electrical
performance
AC withstand test
Partial discharge test
318kV 30min
As 190kV,≤5pC
Supporting insulator
AC/DC withstand test
Impulse test
DC withstand test
Lightning impulse
25kV 1min
As 47.5kV, ±10 times
Creepage distance Minimum flashover distance
Minimum creepage distance
Composite:2175mm
Porcelain:2205mm
Composite:7812mm
Porcelain:7812mm
Pollution level IV

 

The information of dimension and weight

The height of Porcelain:2900mm,the weight of Porcelain:620kg;

The height of Composite:2900mm,the weight of Porcelain:340kg。

the maximum bending moment

The bending moment of Porcelain:36kN•m,the bending moment of Composite:36kN•m。