It’s applicable to connect extruding HV cables to GIS equipment and transformer,it is suitable for XLPE or EPR insulated cables with copper, aluminum or aluminum alloy conductors.
| Voltage (kV) | 170 |
| Insulation Diameter(mm) | Φ50~Φ104 |
| Cross section Area of cable conductor(mm2) | 240-2500mm² |
| The conductor connection method | Crimping Bolt shear |
| Testing items | Testing contents | value |
| AC withstand Test | Dry AC withstand test | 218kV 15min |
| Impulse test | Lightning impulse | 750kV, ±10 times |
| Current carrying capacity | Rate current Short-circuit current |
By cable spec |
| Stress cone electrical performance |
AC withstand test Partial discharge test |
218kV 30min As 131kV,≤5pC |
The information of dimension and weight
| Product’s Type | The height (mm) | The weight (kG) |
| Short Type | 1150 | 55 |
| Long Type | 1430 | 75 |
Please provide the following details to help our sales representatives better understand your needs and get In touch with you as soon as possible.
Connecting Wonderful Life With Optic-Electric Network
Products
Quick Link