170kV GIS/Transformer Termination

It’s applicable to connect extruding HV cables to GIS equipment and transformer,it is suitable for  XLPE or EPR insulated cables with copper, aluminum or aluminum alloy conductors.

Voltage (kV) 170
Insulation Diameter(mm) Φ50~Φ104
Cross section Area of cable conductor(mm2) 240-2500mm²
The conductor connection method Crimping Bolt shear
 
Testing items Testing contents value
AC withstand Test Dry AC withstand test 218kV 15min
Impulse test Lightning impulse 750kV, ±10 times
Current carrying capacity Rate current
Short-circuit current
By cable spec
Stress cone electrical
performance
AC withstand test
Partial discharge test
218kV 30min
As 131kV,≤5pC

The information of dimension and weight

Products Type The height (mm) The weight (kG)
Short Type 1150 55
Long Type 1430 75

Let’s Build The Future with Innovation