It’s applicable to connect extruding HV cables to GIS equipment and transformer,it is suitable for XLPE or EPR insulated cables with copper, aluminum or aluminum alloy conductors.
| Voltage (kV) | 123 |
| Insulation Diameter(mm) | Φ50~Φ104 |
| Cross section Area of cable conductor(mm2) | 240-2000mm² |
| The conductor connection method | Crimping Bolt shear |
| Testing items | Testing contents | value |
| AC withstand Test | Dry AC withstand test | 160kV 15min |
| Impulse test | Lightning impulse | 550kV, ±10 times |
| Current carrying capacity | Rate current Short-circuit current |
By cable spec |
| Stress cone electrical performance |
AC withstand test Partial discharge test |
160kV 30min As 96kV,≤5pC |
The information of dimension and weight
| Product’s Type | The height (mm) | The weight (kG) |
| Short Type | 1150 | 55 |
| Long Type | 1430 | 75 |
It’s applicable to connect extruding HV cables to GIS equipment and transformer,it is suitable for XLPE or EPR insulated cables with copper, aluminum or aluminum alloy conductors.
Please provide the following details to help our sales representatives better understand your needs and get In touch with you as soon as possible.
Connecting the World
Powering the Future
Products
Quick Link