It is applicable to connect extruding HV cables to outdoor electrical equipment and overhead lines,it is suitable for XLPE or EPR insulated cables with copper, aluminum or aluminum alloy conductors.
| Voltage (kV) | 170 |
| Insulation Diameter(mm) | Φ57~Φ100 |
| Cross section Area of cable conductor(mm2) | 240-2500mm² |
| The conductor connection method | Crimping Bolt shear |
| Testing items | Testing contents | value |
| AC withstand Test | Dry AC withstand test | 218kV 15min |
| Impulse test | Lightning impulse | 750kV, ±10 times |
| Current carrying capacity | Rate current Short-circuit current |
By cable spec |
| Stress cone electrical performance |
AC withstand test Partial discharge test |
218kV 30min As 131kV,≤5pC |
| Supporting insulator AC/DC withstand test Impulse test |
DC withstand test Lightning impulse |
25kV 1min As 37.5kV, ±10 times |
| Creepage distance | Minimum flashover distance Minimum creepage distance |
Composite:2175mm Porcelain:2205mm Composite:7812mm Porcelain:7812mm |
| Pollution level | IV |
The information of dimension and weight
The height of Porcelain:2900mm,the weight of Porcelain:620kg;
The height of Composite:2900mm,the weight of Composite:340kg
the maximum bending moment
The bending moment of Porcelain:36kN•m,the bending moment of Composite:36kN•m
Please provide the following details to help our sales representatives better understand your needs and get In touch with you as soon as possible.
Connecting Wonderful Life With Optic-Electric Network
Products
Quick Link